|
Technical Data
Typical Operating Characteristics
Electrical Characteristics
(GRAPH FROM BROCHURE)
Typical Resistance Temperature Characteristic of a Kanthal SiC Heating
Element at Standard Calibration of 1960°F (1071°C)
Kanthal Globar elements have a negative resistance characteristic at
temperatures to approximately 1,200°F (650°C). Above that temperature,
the characteristic changes to positive and remains positive throughout the
normal operating temperature range as shown in the accompanying graph. The
curve as shown from room temperature to 1200°F is an average curve, since
traces of impurities have a noticeable effect on the cold resistance. These
impurities, however, are not a factor in the higher temperature range.
Therefore, nominal resistance ( the value used when making calculations)
is measured at 1960°F (1071°C).
All elements are tested in open air with an electrical loading of 100 watts
per square inch (15.5 watts/cm²). The same test voltage is applied to any
one size and the calibrated current is marked on the right-hand end of
the element as well as on its individual shipping carton. The resistance
of the elements should never be determined at room temperature.
Watt Loading
(GRAPH FROM BROCHURE)
Recommended Watt Loading for Kanthal Globar Elements
The watt load for an element is established by dividing the watt input by the
square area of its radiating surface.
The recommended watt loadings of elements operated at various control temperatures
are given in the accompanying graph.. The upper curve is used to select the number
and size of elements for a given maximum input in atmospheres of air and inert
atmospheres such as argon and helium. The lower curve applies to reducing
atmospheres of hydrogen and nitrogen.
More favorable results can be obtained by conservative watt loadings.. The most
satisfactory service is usually obtained with loadings in the range of 20 to 45
watts per square inch (3.1 to 7 watts per square centimeter) depending on
temperature.
Atmospheres
Kanthal Globar elements can be operated at up to 3000°F (1650°C) in air and inert
atmospheres. The maximum operating temperature for Globar® Type LL elements is
2800°F (1538°C). Some atmospheres at certain temperatures shorten the element's
life.. The dew point of the atmosphere and the watt loading on the element are also
factors that combine to affect element life.
Kanthal Globar elements can be operated at up to 2370°F (1300°C) in hydrogen and
disassociated ammonia atmospheres. In atmospheres containing nitrogen, silicon
nitride will form if a temperature of 2500°F (1370°C) is exceeded. Exothermic gas
can be used up to a carbon monoxide content of 18%. Methane and hydrocarbon vapors
and certain atmospheres reduce element life.
In a carbonaceous atmosphere, Kanthal Globar elements will tend to pick up
carbon. This is a slow process, and the resistance drop can be noted by a
gradual increase in amperage. The carbon has no detrimental effect on the
element. However, it can short-circuit sections of the element, thus increasing
the electrical load on the remaining section and reducing the life. The carbon
can be burned out by shutting off the atmosphere and introducing air into the
furnace chamber at periodic intervals.
Excessive moisture, methane and hydrocarbon vapors should be kept out of the
high-temperature zone of the furnace where the elements are located. The
combination of element watt loading, temperature and atmosphere should be
kept in balance at all times, and recommended limits should not be exceeded.
Atmosphere |
Recommended Operating Limits |
Effect on Element |
|
Temperature |
Watt Loading |
|
Ammonia |
2370°F |
25-30 |
Reduces silica film; forms methane from silicon carbide |
Argon |
Max. |
Max. |
No effect |
Carbon dioxide |
2730°F |
20-25 |
Attacks silicon carbide |
Carbon monoxide |
2800°F |
25 |
Attacks silicon carbide |
Endothermic: 18% carbon monoxide 20% carbon dioxide |
Max. 2500°F
|
Max. 25
|
No effect Carbon pick-up
|
Exothermic |
Max. |
Max. |
No effect |
Halogens |
1300°F |
25 |
Attacks silicon carbide and reduces silica |
Helium |
Max. |
Max. |
No effect |
Hydrocarbons |
2400°F |
20 |
Hot spotting from carbon pick-up |
Hydrogen |
2370°F |
25-30 |
Reduces silica film; forms methane from silicon carbide |
Methane |
2400°F |
20 |
Hot spotting from carbon pick-up |
Nitrogen |
2500°F |
20-30 |
Forms insulating silicon nitrides |
Oxygen |
2400°F |
25 |
Oxidizes silicon carbide |
Sodium |
2400°F |
25 |
Attacks silicon carbide |
Sulfur dioxide |
2400°F |
25 |
Attacks silicon carbide |
Vacuum |
2200°F |
25 |
Below 7 microns, vaporizes silicon carbide |
Water: Dew Point 60°F 50°F 0°F -50°F |
2000°F 2200°F 2500°F 2800°F
|
20-30 25-35 30-40 25-45
|
Reacts with silicon carbide to form silicon hydrates |
Installation Methods
(For Globar® LL, SG, and CRL)
Kanthal Globar elements are easily installed. While they can
be mounted horizontally or vertically, elements should be
mounted centrally in a furnace chamber, and heating sections
should be 1” (25mm) longer than the chamber span. The
conical-shaped ½” (13mm) deep recess in the terminal holes at
the inner wall allows the end of the heating section to radiate
properly and helps maintain uniform temperature within the chamber.
The cold end terminals of elements mounted horizontally lie flat in the
bottom of the terminal hole. Ceramic fiber insulation tucked around
but not under the terminals will prevent heat from escaping through
the terminal holes. Ceramic fiber paper or tubes that extend about
halfway through the furnace wall can be used to prevent terminals
from adhering to the brickwork because of process glazes. The use of
insulating ceramic terminal tubes is recommended. See Element
Accessories section.
(ILLUSTRATION FROM BROCHURE)
Horizontal Installation
Vertically mounted elements should be centered in the terminal holes
and supported by an insulating support at the lower terminal. Bulk
ceramic fiber insulation, tucked around the top and bottom terminals,
prevents a chimney effect. Ceramic fiber flanged tubes can also be used.
Elements must be mounted so they are free to expand and contract,
and not be subject to tension or strain.
(ILLUSTRATION FROM BROCHURE)
Vertical Installation with Arched Roof
(ILLUSTRATION FROM BROCHURE)
Vertical Installation with Flat Roof
Terminal Hole Diameters
To allow sufficient clearance, the element terminal holes should be
in line and of the same diameter shown in the accompanying table
for standard wall thicknesses. Wall abrasion can result from sliding
elements in and out of the chamber. Therefore, the holes through the
insulating board should be enlarged. The terminal hole in the steel
shell should provide sufficient clearance to prevent short circuits.
Terminal Hole Diameters
Element diameter (inches) |
Hole Diameter through Refractory Wall (F) (inches) |
Hole Diameter through Steel Shell (inches) |
Furnace Wall Thickness (inches) |
3 |
5 |
6½ |
7½ |
9 |
13½ |
¼ |
5/16 |
|
|
|
|
|
½ |
5/16 |
7/16 |
7/16 |
|
|
|
|
1 |
3/8 |
½ |
9/16 |
9/16 |
|
|
|
1-¼ |
7/16 |
9/16 |
5/8 |
5/8 |
11/16 |
11/16 |
|
1-½ |
½ |
5/8 |
11/16 |
11/16 |
¾ |
¾ |
|
1-¾ |
5/8 |
13/16 |
13/16 |
7/8 |
7/8 |
7/8 |
|
2 |
¾ |
15/16 |
15/16 |
1 |
1 |
1 |
|
2-¼ |
1 |
1-¼ |
1-¼ |
1-¼ |
1-5/16 |
1-5/16 |
1-3/8 |
2-½ |
1-¼ |
1-½ |
1-½ |
1-½ |
1-9/16 |
1-9/16 |
1-5/8 |
3 |
1-½ |
1-¾ |
1-¾ |
1-13/16 |
1-13/16 |
1-13/16 |
1-7/8 |
3- |
1-¾ |
2 |
2 |
2-1/16 |
2-1/16 |
2-1/8 |
2-3/16 |
4 |
2-1/8 |
2-3/8 |
2-3/8 |
2-7/16 |
2-7/16 |
2-9/16 |
2-5/8 |
4-¾ |
Recommended Element Spacing
To allow for the most efficient radiation, the minimum distance
between element centers should be twice the element diameter. The
minimum distance from the center line of an element to any wall
should not be less than 1- times the element diameter. The
recommended spacing for all Kanthal Globar elements is shown in
the accompanying diagram.
(DIAGRAM FROM BROCHURE)
Recommended Element Spacing Guidelines
Connections
Care must be used when placing the terminal straps and clamps on
elements to help prevent breakage.
An aluminum strap should be wrapped around the terminal end of
LL or SG elements and held in place by either M or C type spring clamps.
Type M clamps with wings are used when there is enough space available
for the clamp to be fitted on the element without shorting of the electrical
connection.. When the C clamp is required, the expanding tool is used to fit
on the element in order to avoid mechanical shock.
Enough slack should be left in the straps to allow for
element expansion.
Sufficient clearance should be left between the two when the
furnace is up to temperature.
Installation Methods for SGR Elements
Kanthal Globar SGR elements can be mounted horizontally or vertically,
projecting up or hanging down. The terminal assembly should be outside
the furnace structure to keep it as cool as possible. No portion of the
spiral heating section should extend into the refractory wall.
The element should be mounted in an insulating ceramic terminal
tube to prevent possible shorting of the terminal ends, because
full element voltage exists along the entire length of the terminal.
The element should be mounted as shown in the accompanying diagrams.
The slot in the terminal should not be in contact with the terminal
tube or brickwork.
The terminal slot must remain free of any electrical conducting material,
such as condensed metallic vapors, carbon, ceramic glazes, and other
materials which lose their electrical insulating properties at high
temperatures.
In some installations where elements are mounted horizontally, it
may be necessary to support the tip end of the element in a blind
hole drilled in the opposite wall of the chamber. The blind hole
should be at least ½” (13mm) larger in diameter than the element
and have a ½” deep conical recess for easy element installation.
Special SGR elements, with longer, unspiraled sections at the
extremity of the element should be used for this type of installation.
Recommended Element Spacing
Recommended element spacing for SGR elements is the same as for LL, SG and
CR elements. Click here for details.
Terminal Hole Diameters
Recommended terminal hole diameters for all Kanthal Globar elements are
shown in the accompanying table. However, insulating ceramic terminal
tubes are highly recommended for use with SGR elements. When insulating
ceramic terminal tubes are used, the diameter of the holes through the
chamber wall is determined by the outside diameter of the terminal tube.
When properly installed, the element, terminal tube and terminal hole
should all have a snug fit. Click here for terminal tube dimensions.
(DIAGRAM FROM BROCHURE)
Horizontal
(DIAGRAM FROM BROCHURE)
Horizontal into Blind Hole
(DIAGRAM FROM BROCHURE)
Hanging Down
(DIAGRAM FROM BROCHURE)
Projecting Up
Physical Specifications
(DIAGRAM FROM BROCHURE)
Element diameter (inches) |
Dimensions (inches) |
Terminal Strap Ampere Rate |
D |
F |
T |
V |
W |
½ |
1-¾ |
½ |
1 |
1 |
2-1/8 |
25 |
5/8 |
1-¾ |
½ |
1 |
1 |
2-1/8 |
25 |
¾ |
2-¼ |
½ |
1 |
1 |
2-1/8 |
25 |
1 |
2-¼ |
½ |
1 |
1 |
2-1/8 |
50 |
1-¼ |
3 |
½ |
1-½ |
1 |
2-5/8 |
50 |
1-½ |
3 |
¾ |
1-½ |
1 |
2-5/8 |
50 |
1-¾ |
3-½ |
¾ |
1-½ |
1 |
2-5/8 |
100 |
2-1/8 |
4 |
1 |
1-½ |
1 |
2-5/8 |
100 |
|